Transformers and the National Grid: Why Electricity Travels at High Voltage
See why sending electricity at high voltage cuts the energy wasted in cables, how a transformer changes an alternating p.d., and how to use Vp/Vs = Np/Ns and VpIp = VsIs with confidence.
Published · 7 min read
On this page
Electricity is sent across a country at a very high voltage because this keeps the current in the cables small. A small current wastes far less energy heating the cables. For the same power, P = IV, so raising the p.d. lowers the current. The heating in a cable of resistance R is:
The current is squared. So if the voltage goes up 16 times, the current falls to one-sixteenth and the heating loss falls to 1/256 of its old value.
The National Grid carries electricity from power stations to homes, offices and factories across the country, along overhead and underground cables with transformers on the way. Step-up transformers at the power station raise the p.d. for the long-distance cables. Step-down transformers near the users bring it back down to a safer level. Transformers only work with alternating current (a.c.).
How does the National Grid get electricity to your home?
The journey has three main stages:
- Power station. Generators produce a.c., typically at between about 11 kV and 25 kV. A step-up transformer raises this to a very high p.d. for transmission.
- Transmission lines. Overhead cables on pylons carry the power across the country. In the UK these lines mostly run at 275 kV or 400 kV. Pakistan's national grid uses 500 kV and 220 kV lines, and India's includes lines at 765 kV.
- Substations. Step-down transformers lower the p.d. in stages, for example to 132 kV, 33 kV and 11 kV, and finally to the 230 V supply in a home.
Factories that need a lot of power often take their supply at a higher voltage and step it down themselves.
Why does high voltage waste less energy?
Every cable has some resistance, so a current heats it. That energy is lost to the surroundings. Because the heating depends on the square of the current, the best way to cut the loss is to make the current small. A higher voltage does exactly this for the same power.
Worked example 1: the same power at two voltages
A power station sends 100 MW through transmission cables with a total resistance of 2.0 Ω. Find the power wasted in the cables if the power is sent (a) at 25 kV and (b) at 400 kV.
Given: P = 100 MW = W, R = 2.0 Ω
Equations: for the current, then for the power wasted
(a) A
Power wasted: W, which is 32 MW
(b) A
Power wasted: W, which is about 0.13 MW
Answer: At 25 kV, almost a third of the power would be lost. At 400 kV, only about 0.13% is lost. The voltage is 16 times higher, so the loss is times smaller.
A smaller current also means thinner, lighter, cheaper cables can be used. Higher voltages need tall pylons and good insulation, but the savings far outweigh these costs.
What is a transformer made of?
A simple transformer has three parts:
- a primary coil, connected to the input supply
- a secondary coil, connected to the output
- a soft iron core that both coils are wound around
The two coils are not connected to each other by any wire. The core is made of soft iron because it magnetises and demagnetises very easily.
How does a transformer work?
- An alternating current in the primary coil produces a magnetic field in the iron core that keeps changing in size and direction.
- The core carries this changing field through the secondary coil.
- A changing magnetic field through a coil induces a p.d. across it. So an alternating p.d. appears across the secondary coil.
This is electromagnetic induction. If you connect a battery to the primary coil instead, the current is steady, so the field does not change. No p.d. is induced, except for a brief pulse at the moment you switch on or off. That is why transformers need a.c.
Explore these ideas in the transformers and National Grid simulation.
How do you use the turns-ratio equation?
The p.d.s across the two coils are in the same ratio as their numbers of turns:
- Step-up transformer: more turns on the secondary, so is bigger than .
- Step-down transformer: fewer turns on the secondary, so is smaller than .
Worked example 2: a 12 V lighting transformer
A garden lighting kit in Birmingham uses a transformer to step 230 V mains down to 12 V. The primary coil has 4600 turns. How many turns does the secondary coil need?
Given: = 230 V, = 12 V, = 4600
Equation: , rearranged to
Substitution:
Answer: = 240 turns
Check: 230 ÷ 12 and 4600 ÷ 240 both come to about 19.2, so the two ratios match.
What happens to the current in a transformer?
A transformer cannot create energy. A perfect, 100% efficient transformer would give out exactly as much power as it takes in:
So a step-up transformer raises the p.d. but lowers the current by the same factor. A step-down transformer lowers the p.d. and raises the current. Real transformers lose a little energy as heat in the coils and the core. The big ones in substations waste less than 1% of the power passing through them.
Worked example 3: current from the mains
The 12 V transformer in worked example 2 lights a set of lamps that take a current of 4.0 A. Assuming it is 100% efficient, find the current drawn from the 230 V mains.
Given: = 12 V, = 4.0 A, = 230 V
Equation: , rearranged to
Substitution:
Answer: = 0.21 A (2 significant figures)
The output power is 12 × 4.0 = 48 W. The mains supplies the same 48 W, but at a much higher p.d., so it needs a much smaller current.
Worked example 4: back at the power station
A step-up transformer at a power station takes 100 MW at 25 kV and gives out 400 kV. Its primary coil has 500 turns. Assume it is 100% efficient. Find (a) the number of turns on the secondary coil and (b) the current in each coil.
Given: = 25 000 V, = 400 000 V, = 500, P = W
(a) Equation:
Substitution:
Answer: = 8000 turns
(b) Equation: for each coil, since
Primary: A
Secondary: A
The p.d. goes up 16 times and the current goes down 16 times. These are the two currents from worked example 1.
The electromagnetic induction simulation covers the effect that makes transformers possible.
Common mistakes
- Using P = V²/R with the transmission voltage. The 400 kV is not the p.d. across the cable. Find the current first, then use .
- Turning the ratio upside down. Put both primary values on top, or both on the bottom.
- Thinking a step-up transformer increases the power. It raises the p.d. but lowers the current. At best the power stays the same.
- Saying transformers work with d.c. A steady current gives a steady field, which induces nothing.
- Forgetting to convert kV and MW. 400 kV is 400 000 V, and 100 MW is 100 000 000 W.
Key points
- Electricity is transmitted at high voltage so that the current is small. This cuts the heating loss, , in the cables.
- Step-up transformers raise the p.d. at power stations. Step-down transformers lower it for homes and businesses.
- A transformer has a primary coil and a secondary coil on a soft iron core. It works only with a.c.
- Turns ratio: .
- For a 100% efficient transformer, . Raising the p.d. lowers the current.