What this topic covers
Live, neutral and earth (Core)
The live (or line) wire is at a high alternating p.d. The neutral wire is the return path, at about 0 V. The earth wire is joined to any metal casing and carries a current only in a fault. In the UK these are brown, blue, and green and yellow, and the mains is nominally 230 V at 50 Hz.
The switch goes in the live wire, so that opening it disconnects the appliance from the high p.d. A switch in the neutral would leave the parts inside live when off.
Four hazards (Core)
- Damp. Impure water conducts, so wet skin or floors let current pass more easily through someone to earth.
- Overloading. Appliances sharing one socket, adaptor or extension lead are in parallel, so their currents add. Too large a total overheats the plug, socket or lead.
- Damaged insulation. A cracked cable can expose a live conductor (a shock risk) or let live touch neutral: a short circuit.
- Overheating cables. Too much current for a cable, or a lead left coiled up, can make it hot enough to melt its insulation and start a fire.
Fuses and trip switches (Core)
A fuse is a thin wire in a holder, placed in the live wire. If the current rises above its rating, the wire melts and breaks the circuit; the fuse must then be replaced.
A trip switch (circuit breaker) is an automatic switch in the live wire. In a common design, too large a current makes an electromagnet strong enough to pull an iron catch, and spring-loaded contacts then snap open. It acts faster than a fuse, and after the fault is fixed it is reset, not replaced.
Find the normal current from and choose the smallest fuse rating above it. Too low, and the fuse melts in normal use. Too high, and a fault current that overheats the cable might not melt it. A trip switch is set the same way: above the largest normal current, but within what its cables can carry.
Worked example (Core): a fan heater
A 2.0 kW fan heater runs on a 230 V supply. Choose from fuses of 1 A, 3 A, 5 A, 10 A and 13 A.
Given: kW W, V
Equation: , so
Substitution:
Answer: A. A 5 A fuse is too small for everyday use. Choose 10 A, the smallest rating above 8.7 A. A 2.5 kW kettle takes 10.9 A, so it needs 13 A.
Earthed or double-insulated (Core)
A metal casing must be earthed. If a loose live wire touches it, a large current flows to earth along the low-resistance earth wire. This melts the fuse, or opens the trip switch, cutting the casing off from the live supply. Unearthed, it would stay at the mains p.d., a shock hazard.
A double-insulated appliance has an insulating outer casing, such as plastic, so it cannot become live and needs no earth wire. Its fuse still protects the circuit and the cable: if live touches neutral inside, the large current melts it.
In the simulation above
The Plug scene, shown first, goes beyond the syllabus.
- Press Faults under the stage. With Earthed metal case, press Fault: about 230 A flows in the earth wire until the kettle's 13 A fuse melts. Then pick No earth wire and press Fault again: the fuse survives, but the Case card shows 230 V.
- Choose Double insulated (a hairdryer with a 5 A fuse) and press Fault: no fault current flows. Under Fault, pick Short circuit and press the Fault button: the fuse melts, with no earth wire at all.
- Press Fuse and pick Fan heater (2 kW) under Appliance. Choose 5 A and press Switch on: it melts in normal use. Choose 10 A, press Switch on, then Fault: the overload melts it.
- Press Home and choose Kettle and heater on together from Examples: 19.6 A trips the sockets circuit's 16 A trip switch. Turn off Fan heater (2 kW), then press Reset.