Where this sits in AQA GCSE Physics
Spec points 4.2.3.1 and 4.2.3.2 are tested on both tiers, for Combined Science students as well as GCSE Physics students. They bring no new equation; the worked example borrows (4.2.1.3, recall).
Direct or alternating?
A cell gives a direct p.d.: one terminal is always the positive one, so the current always flows the same way. An alternating p.d. keeps reversing, and so does the current it drives.
Mains electricity is a.c. In the UK it alternates at 50 Hz, meaning 50 complete cycles each second, and its p.d. is about 230 V. Both are nominal values.
The three cores
A three-core cable links most appliances to the mains, each core in its own colour of insulation.
| Core | Insulation | Its job | p.d. compared with earth |
|---|---|---|---|
| live | brown | connects the appliance to the supply's alternating p.d. | about 230 V |
| neutral | blue | the return path to the supply | 0 V, or very nearly |
| earth | green and yellow stripes | joined to a metal case, so a fault cannot leave the case live | 0 V; no current unless something goes wrong |
Why live is dangerous
Your body is normally at about 0 V, like the ground. If you touch the live wire, roughly 230 V is across you, so a current flows through your body to earth. No neutral is needed: you complete the circuit.
Opening a switch breaks the circuit in just one place. The live wire on the supply side of it, such as the wall wiring, stays at about 230 V. A switch wrongly fitted in the neutral leaves the whole appliance live when it is off.
Any link between live and earth has the full mains p.d. across it. Through a person, the current can kill. Through a path of very low resistance, the current is huge: it heats the wiring and could start a fire.
Worked example: a live core touches a metal case
A toaster's live core rubs through its insulation and touches the metal case. Explain what happens (a) if the case is earthed and (b) if the earth wire has come loose and someone touches the case. In (b), the path through the person and the floor has a resistance of 4600 Ω, a model value.
(a) Earthed case
- The earth wire holds the case close to 0 V, so it does not become live.
- Live is now joined to earth through a path of very little resistance.
- A very large current flows in the earth wire, the only time it carries one.
- Not in the AQA specification: this current melts the fuse or trips a circuit breaker, cutting off the live supply.
(b) No earth connection
- No extra current flows, so the toaster may seem fine.
- The case is now at about 230 V: it is live.
- The person is at about 0 V, so touching the case puts 230 V across their body.
- Current: A
Answer: in (a) the fault current goes down the earth wire, not through anyone. In (b), 50 mA flows through the person, which can be fatal.
In the simulation above
It opens on the Plug scene, which goes beyond AQA. Press Faults under the stage: a metal kettle is switched on, with Earthed metal case chosen.
- In the earth wire reads 0 A. Press Fault: it leaps to about 230 A until the 13 A fuse melts, then drops to 0 A, and the Case card reads 0 V.
- Choose No earth wire and press Fault. The fuse stays whole, but the Case card shows the case at 230 V.
- Press Switch off, then Fault. The status line explains why switching off did not help.
- Press Home and choose Light switch in the neutral from Examples. Every light is off, yet Light 1's holder is still at 230 V. Set Light 1’s switch is wired into the to Live wire and it drops to 0 V.