Who needs this: every AQA student
Spec point 4.2.4.3 is for everyone: Foundation and Higher, Physics and Combined Science alike. It has no equation of its own. Instead, you explain it with two equations you must recall from 4.2.4.1, and . Be ready to:
- say what job the National Grid does
- name its two kinds of transformer, where each one goes and what each does to the potential difference
- explain, step by step, why sending energy at a very high p.d. wastes so little of it
How transformers work, and the transformer equations, are Higher tier and GCSE Physics only (4.7.3.4). They are on the Transformers page.
From power station to plug
The National Grid is the network that delivers electrical power to the places where it is used: homes, schools, shops and factories. Its cables hang from pylons or run underground, with transformers at each end.
- At the power station, step-up transformers increase the potential difference to a very high value before the energy enters the transmission cables.
- The cables carry the energy across the country.
- Near the users, step-down transformers in substations lower the p.d. in stages, until it reaches the mains value of about 230 V used at home.
Transformers only work with alternating current, and UK mains is a.c. at 50 Hz. In Britain the main lines typically run at 400 kV or 275 kV, with 132 kV lines serving regions. You do not need to learn these values.
Why the p.d. is made so high
Every cable has resistance, so the current in it heats the cable. That energy is dissipated to the surroundings and wasted. A very high p.d. keeps this loss small, through three linked steps:
- For the same power, shows that a higher p.d. needs a smaller current.
- The heating power in the cables is . It depends on the current squared, so a current ten times smaller heats the cables a hundred times less.
- Less energy is wasted, so more of the energy sent out reaches the users. That is why the grid is efficient.
A small current has a second benefit, separate from efficiency: thinner cables can carry it without overheating, which saves money and material.
Step-down transformers then lower the p.d. because such a high value would be extremely dangerous inside buildings.
Worked example: one power, two potential differences
A power station sends 40 MW to a city through cables with a total resistance of 3.0 Ω. Compare sending it at 20 kV with sending it at 400 kV.
Given: W, .
Equations: , rearranged from ; then heating power .
At 20 kV: A, so the heating power is W, or 12 MW.
At 400 kV: A, so the heating power is W, or 30 kW.
Answer: at 20 kV, 12 MW of the 40 MW is wasted, so the cables transfer energy with an efficiency of only . At 400 kV the loss is 30 kW and the efficiency is about 99.9%. The p.d. is 20 times higher, the current is 20 times smaller and the heating is times smaller.
Try the grid yourself
In the simulation above, the transformer view loads first. Press Grid, under the stage, to open the National Grid. Its power station always sends out 100 MW, generated at 25 kV, and at first nothing steps the p.d. up.
- Read Current in the lines: 4000 A. Heating the lines shows 32.0 MW, so only 68.0 MW reaches the homes and three of the ten houses stay dark.
- Predict the current at 132 kV, then press Raise to check: 758 A, and the heating falls to 1.15 MW.
- Press Raise twice more, to 400 kV. The p.d. is now 16 times the generators' 25 kV, so the current is 16 times smaller (250 A) and the heating 256 times smaller (0.125 MW). The same 100 MW at each p.d. shows all four results side by side.
- Drag Resistance of the lines (model) to 0 Ω. Nothing is wasted at any p.d., which shows that the loss comes from the cables' resistance.